Appendix 4-A - Interpretation of Legionella Culture Results from Cooling Towers
Effective Date
Appendix 4-A
| Interpretation of Legionella Culture Results from Cooling Towers | |
| Legionella Test Results in CFU/mL1 |
Response
|
| No detection (< 20 CFU/mL) | Maintain treatment program and Legionella monitoring in accordance with the maintenance program and plan. |
| For levels at ≥ 20 CFU/mL but < 1000 CFU/mL perform the following: |
o Review treatment program.
o If retest is ≥ 1000 CFU/mL, undertake control strategy as noted below.
|
| For levels ≥ 1000 CFU/mL perform the following: |
o Review the treatment program and provide appropriate notifications per section 4-1.6 of this Subpart.
|
| 1 Colony forming units per milliliter.
2 Online disinfection means – Dose the cooling tower water system with either a different biocide or a similar biocide at an increased concentration than currently used. 3 Online decontamination means – Dose the recirculation water with a halogen-based compound (chlorine or bromine) equivalent to at least 5 milligrams per liter (mg/L) or parts per million (ppm) free residual halogen for at least one hour. 4 System decontamination means – Maintain between 5 to 10 mg/L (ppm) free residual halogen for a minimum of one hour; drain and flush with disinfected water; clean wetted surface; refill and dose to 1 – 5 mg/L (ppm) of free residual halogen and circulate for 30 minutes. Refill, re-establish treatment and retest for verification of treatment. NOTE: Stabilized halogen products should not be used for online decontamination or system decontamination as defined in this Appendix per footnotes 3 and 4. |
|